TCI-W11-U, TCI-W22-U Universal Controller
OVERVIEW
Doc: 70-00-0140C, V2.0-20220523 © Vector Controls LLC, USA Page 1-24
Subject to alteration
TCI-W11-U, TCI-W22-U Series Wall Mounted Universal Controller
Features
• Universal PID and/or binary control for any analog input/output
signal and range.
• Multiple auxiliary functions: heat-cool auto changeover,
automatic enable, setpoint compensation.
• Differential, averaging, min and max functions
• Cascading of control loops (-W22 type).
• Alarm monitoring of low and high limits on all inputs.
• Programmable reaction in case of alarm.
• Feedback function for inputs and set points.
• Functions for dehumidifying, set point shift, cascade control.
• Password protected programmable user and control parameters.
• Blue backlight
TCI-W22-U also includes
• Power Cap protected real-time clock with 48hr power backup.
• Clock with up to 8 switching events
• 7-day programmable schedules, with options including change of
setpoints and direct position of manual outputs.
• Fan coil units
• Heat exchangers
• Zoning
• VAV
• Air handlers
• Fan, Pump control
• Humidifiers
• Dehumidifiers
• Ventilation
• Radiant heating
• Radiant cooling
• Pressurization
General
• TCI-W11-U: 1 independent control loop, 1 internal temperature sensor, 1 universal input (analog/binary/temp), 2
binary/PWM outputs, 1 analog output
• TCI-W22-U: 2 independent control loops, 8 time schedules, 1 internal temperature sensor, 2 universal inputs,
2 binary/PWM outputs, 1 analog output
• Internal temperature sensor standard. Add replaceable humidity element as required: AES3-HT-A2 (2%), AES3-HT-
A3 (3%), or AES3-HT-A5 (5%)
• Flexible application configuration is made with a parameter-setting routine using the standard operation terminal.
Product Name
Types and Ordering
Temperature
Sensor
(internal)
Humidity
Sensor
(internal)
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy:SDB-Tn10-20 (duct), SRA-Tn10
(room), SDB-Tn10-20 + AMI-S10 as immersion sensor.
Actuators: Choose modulating actuators with an input signal type of 0-10 V DC or 4-20 mA (Min. and max. signal limitations
may be set with parameters.3-pointpoint actuators with constant running time are recommended.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, humidifiers, etc): Do not directly connect devices that exceed
specified limits in technical specifications – observe startup current on inductive loads.
Housing Blank = square housing
In/Outputs:
Control loops: 1 = 1 control loop, 2 = 2 control loops
Mounting: W = Wall mounted
Series: TCI