14
This alarm occurs when an error has been made in program-
ming. In Version 17 and later, this will also occur if the line length
has not been programmed. The line length default is 501 feet
and will cause a SETUP DATA WARNING if the Service Contrac-
tor does not enter the line length.
NOTE: The default line type is set to FLEX A (white Envirof-
lex PP1501). If the actual line type is not FLEX A, and the
Service Contractor does not select the correct line type, the
result may be a GROSS LINE FAIL.