15
TABLE I - High Pressure Thresholds & Warning/Alarm
Software Version
High Pressure Limit
15 40 psi warning
50 psi alarm & shutdown
16 A & B 40 psi warning
50 psi alarm & shutdown
16 C 29 psi warning
30 psi alarm & shutdown
17 & 18 30 psi warning
40 psi alarm & shutdown
19 Not Applicable
TABLE II - Typical Line Pressure
STP Status
Pressure Range Gauge vs. Console
Off 17 - 25 psi ±5 psi
On >25 psi ±5 psi