EasyManuals Logo
Home>YASKAWA>Controller>CIPR-GA50C series

YASKAWA CIPR-GA50C series User Manual

YASKAWA CIPR-GA50C series
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
1 English
36 YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Note:
When it is necessary to ramp to stop the motor, do not turn off terminals H1 and H2 until the motor fully stops. This
will prevent the motor from coasting to stop during usual operation.
A maximum of 3 ms will elapse from when terminals H1 or H2 shut off until the drive switches to the "Safe Torque
Off" status. Set the OFF status for terminals H1 and H2 to hold for at least 3 ms. The drive may not be able to switch
to the Safe Torque Off status if terminals H1 and H2 are only open for less than 3 ms.
Going from “Safe Torque Off” to Usual Operation
The safety input will only release when there is no Run command.
During Stop
When the Safe Disable function is triggered during stop, close the circuit between terminals
H1-HC and H2-HC to disable Safe Torque Off. Enter the Run command after the drive
stops correctly.
During Run
When the Safe Disable function is triggered during run, close the circuit between terminals
H1-HC and H2-HC to disable Safe Torque Off after clearing the Run command. Enter the
Stop command, then enter the Run command when terminals H1 and H2 are ON or OFF.
Validating the Safe Disable Function
After you replace parts or do maintenance on the drive, complete all necessary wiring to start the
drive, then follow these steps to test the Safe Disable input. Keep a record of the test results.
1. When the two input channels are OFF (Open), make sure that the keypad flashes STo [Safe
Torque OFF], and make sure that the motor is not running.
2. Monitor the ON/OFF status of the input channels and make sure that MFDO set to the
EDM function operates as shown in Table 1.11.
If one or more of the these items are true, the ON/OFF status of the MFDO may not display
correctly on the keypad.
Incorrect parameter settings.
A problem with an external device.
The external wiring has a short circuit or is disconnected.
There is damage to the device.
Find the cause and repair the problem to correctly display the status.
3. Make sure that the EDM signal operates during usual operation as shown in Table 1.11.
Safe Disable Monitor Output Function and Keypad Display
Refer to Table 1.11 for information about the relation between the input channel status, Safety
monitor output status, and drive output status.

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals