Johnson Controls Unitary Products 5
697887-YTG-H-0514
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
80% 90% 100% 110% 120%
Capacity Factor
0.96 0.98 1.00 1.02 1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY
Models
AHE18B
(6ELE6)
AHE22B
AHE24B
(6ELE7)
AHE30B
(6ELE8)
AHE34C
AHE36C
(6ELE9)
AHE42D
(6ELF0)
AHE48D
(6ELF1)
AHE60D
(6ELF2)
Blower - Diameter x Width 10 x 8 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
Motor
HP 1/3 HP 1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP
Nominal RPM 1050 1050 1050 1050 1050 1050 1050 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230V
2.8 2.8 2.8 2.8 4.1 4.1 4.1 6.0 6.0
Filter
1
Type DISPOSABLE OR PERMANENT
Size 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1
Permanent Type Kit 1PF0601BK 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK
Shipping /
Operating Weight (lbs.)
115/103 120/105 120/105 120/105 152/137 152/137 168/150 171/153 174/156
1. Field supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by
the conversion factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
220V 240V 0.84
ELECTRICAL DATA - COOLING ONLY
Models
Motor FLA
1
Minimum Circuit
Ampacity
MOP
2
Minimum Wire Size (AWG)
3
AHE18B / AHE22B /
AHE24B / AHE30B
2.8 3.5 15 14
AHE34C / AHE36C / AHE42D 4.1 5.1 15 14
AHE48D / AHE60D 6.0 7.5 15 14
1. FLA = Full Load Amps
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75C, copper wire only. If wire other than non-plated, 75C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
ELECTRICAL HEAT: MINIMUM FAN SPEED
1
Heater Kit Models
2,3
Nom. kW
@240V
Air Handler Models
AHE18B
AHE22B
AHE24B
AHE30B
AHE34C
AHE36C
AHE42D AHE48D AHE60D
6HK(0,1)6500206 2.4kW Med Low #2 Med Low #2 Low #1 Med #3 Low #1 Med Low #2 Med Low #2
6HK(0,1)6500506 4.8kW Med Low #2 Med Low #2 Med Low #2 Med Low #2 Med #3 Med #3 Med Low #2
6HK(0,1)6500806 7.7kW Med High #4 Med High #4 Med #3 Med #3 Med #3 Med #3 Med Low #2
6HK(0,1)6501006
6HK06501025
9.6kW Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med #3
6HK(1,2)6501306 12.5kW - Med High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med #3
6HK(1,2)6501506
6HK06501525
14.4kW - High #5 High #5 Med High #4 Med High #4 Med High #4 Med #3
6HK(1,2)6501806
6HK06501825
17.3kW - - - High #5 High #5 High #5 Med High #4
6HK(1,2)6502006
6HK16502025
19.2kW - - - High #5 High #5 High #5 High #5
6HK(1,2)6502506
6HK16502525
24kW------High #5
1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
3. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.