035-16004-001-A-0202
8 Unitary Products Group
TABLE 6 - ELECTRICAL DATA (BASIC UNIT)
MODEL
BHA
POWER SUP
-
PLY
VOLTAGE
LIMITATIONS
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN. MAX. RLA LRA
018 208/230-1-60 187 253 9.0 48.0 1.1 2.6 14.9 20 20 .96 40
024 208/230-1-60 187 253 11.2 60.0 1.1 2.6 17.7 25 25 .96 40
030 208/230-1-60 187 253 12.0 73.0 1.1 2.6 18.7 25 25 .96 40
036 208/230-1-60 187 253 17.3 94.0 1.1 3.5 26.2 35 35 .96 40
042 208/230-1-60 187 253 20.5 120.0 1.1 3.5 30.2 40 40 .96 40
048 208/230-1-60 187 253 24.4 140.0 1.5 4.0 36.0 50 50 .96 40
060 208/230-1-60 187 253 28.9 165.0 1.5 7.0 44.6 60 60 .96 40
036 208/230-3-60 187 253 10.9 78.0 1.1 3.5 18.2 25 25 .96 75
042 208/230-3-60 187 253 14.1 110.0 1.1 3.5 22.2 30 30 .96 75
048 208/230-3-60 187 253 14.1 105.0 1.5 4.0 23.1 30 30 .96 75
060 208/230-3-60 187 253 16.0 125.0 1.5 7.0 28.5 40 40 .96 75
036 460-3-60 414 504 5.8 40.0 0.6 1.8 9.6 15 15 .96 75
042 460-3-60 414 504 7.1 54.0 0.6 1.8 11.2 15 15 .96 75
048 460-3-60 414 504 7.1 55.0 0.8 2.0 11.7 15 15 .96 75
060 460-3-60 414 504 8.0 67.0 0.8 3.5 14.3 20 20 .96 75
036 575-3-60 518 630 4.5 32.0 0.4 1.5 7.6 15 15 .96 75
042 575-3-60 518 630 5.8 44.0 0.4 1.5 9.1 15 15 .96 75
048 575-3-60 518 630 5.6 44.0 0.6 1.6 9.3 15 15 .96 75
060 575-3-60 518 630 6.4 50.0 0.6 2.8 11.4 15 15 .96 75
= Rated in accordance with ARI Standard 110, utilization range “A”.
= Dual element, time delay type.