036-21490-002-A-0204
24 Unitary Products Group
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 14: ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
2
STAGES AMPS
BP180
208 21.8 184 4.5 15.4 10.0
- 0.0 - - 83.5 100
E18 13.5 1 37.5 130.3 150
E36 27.0 2 75.1 130.3 150
E54 40.6 2 112.6 172.6 175
E72 54.1 2 150.1 181.9 200
230 21.8 184 4.3 14.4 10.0
- 0.0 - - 82.1 100
E18 18.0 1 43.3 136.2 150
E36 36.0 2 86.6 138.8 150
E54 54.0 2 129.9 160.4 175
E72 72.0 2 173.2 203.7 225
460 11.0 90 2.2 7.2 5.0
- 0.0 - - 41.4 50
E18 18.0 1 21.7 68.4 70
E36 36.0 2 43.3 69.4 70
E54 54.0 2 65.0 80.2 90
E72 72.0 2 86.6 101.9 110
575 9.3 73 1.7 5.9 4.0
- 0.0 - - 34.2 40
E18 18.0 1 17.3 55.8 60
E36 36.0 2 34.6 55.9 60
E54 54.0 2 52.0 64.3 70
E72 72.0 2 69.3 81.7 90
BP240
208 33.6 225 3.7 20.0 10.0
- 0.0 - 0.0 120.4 150
E18 13.5 1.0 37.5 167.2 175
E36 27.0 2.0 74.9 167.2 175
E54 40.6 2.0 112.7 178.4 200
E72 54.1 2.0 150.2 214.1 225
230 33.6 225 3.7 20.0 10.0
- 0.0 - 0.0 120.4 150
E18 18.0 1.0 43.3 174.5 175
E36 36.0 2.0 86.6 174.5 175
E54 54.0 2.0 129.9 174.5 175
E72 72.0 2.0 173.2 228.7 250
460 17.3 114 1.9 10.0 5.0
- 0.0 0 0.0 61.5 70
E18 18.0 1.0 21.7 88.6 100
E36 36.0 2.0 43.3 88.6 100
E54 54.0 2.0 65.0 88.6 100
E72 72.0 2.0 86.6 115.7 125
575 13.5 80 1.5 8.2 4.0
- 0.0 - 0.0 48.6 60
E18 18.0 1.0 17.3 70.2 80
E36 36.0 2.0 34.6 70.2 80
E54 54.0 2.0 52.0 70.2 80
E72 72.0 2.0 69.3 91.9 100