036-21489-001-C-1004
Unitary Products Group 23
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 11: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
2
STAGES AMPS
BQ240
208 16.7 150 4.5 19.4 0.0
- 0.0 - - 100.1 110
E18 13.5 1 37.5 146.9 150
E36 27.0 2 75.1 146.9 150
E54 40.6 2 112.6 165.1 175
E72 54.1 2 150.1 193.7 200
230 16.7 150 4.3 21.0 0.0
- 0.0 - - 101.7 110
E18 18.0 1 43.3 155.8 175
E36 36.0 2 86.6 155.8 175
E54 54.0 2 129.9 156.2 175
E72 72.0 2 173.2 209.9 225
460 9.6 75 2.2 9.7 0.0
-0.0 - - 54.9 60
E18 18.0 1 21.7 82.0 90
E36 36.0 2 43.3 82.0 90
E54 54.0 2 65.0 82.0 90
E72 72.0 2 86.6 109.1 110
575 6.4 62 1.7 7.8 0.0
-0.0 - - 38.8 45
E18 18.0 1 17.3 60.4 70
E36 36.0 2 34.6 60.4 70
E54 54.0 2 52.0 61.7 70
E72 72.0 2 69.3 82.1 90