FORM 100.50-EG1
21
YORK INTERNATIONAL
TABLE 7 50 THROUGH 65 TON EXHAUST FAN DATA
TOTAL STATIC PRESSURE (inches of water column)
CFM 0.50 1.00 1.50 2.00 2.50 3.00
STD. AIR RPM HP RPM HP RPM HP RPM HP RPM HP RPM HP
10000 674 3.30 801 4.18 –– –– –– –– –– –– –– ––
12000 713 4.84 823 5.82 929 6.87 –– –– –– –– –– ––
14000 762 6.84 858 7.98 952 9.12 1043 10.32 1132 11.62 –– ––
16000 819 9.36 904 10.73 988 12.04 1070 13.33 1150 14.69 1229 16.10
18000 879 12.42 957 14.04 1032 15.56 1107 17.02 1179 18.48 –– ––
20000 943 16.18 1014 18.04 –– –– –– –– –– –– –– ––