UNIT COOLING CAPACITIES AND POWER REQUIREMENTS
Model
HCE
Suction Press. & Corresponding
Temp. @ Saturation
Temperature of Air on Condenser Coil,
°F
65 75 85 95 105 115
PSIG
°F
MBH KW* MBH KW* MBH KW* MBH KW* MBH KW* MBH KW*
090
61.6 35 98 7.0 92 7.2 85 7.4 78 7.6 71 7.8 64 8.1
68.5 40 108 7.5 101 7.7 94 7.9 87 8.1 80 8.4 72 8.7
76.0 45 116 7.9 109 8.1 102 8.3 95 8.6 87 8.9 79 9.3
84.0 50 123 8.2 116 8.4 109 8.7 102 9.0 94 9.4 86 9.9
120
61.6 35 134 10.0 126 10.3 117 10.6 108 10.9 98 11.2 88 11.6
68.5 40 148 10.7 139 11.0 129 11.3 119 11.6 109 11.9 99 12.4
76.0 45 160 11.2 150 11.5 140 11.8 130 12.2 120 12.6 110 13.1
84.0 50 170 11.6 159 11.9 149 12.3 139 12.7 129 13.2 119 13.8
150
61.6 35 140 9.4 133 10.4 127 11.3 119 12.6 112 13.8 105 15.1
68.5 40 151 9.6 144 10.6 137 11.5 129 12.8 122 14.1 114 15.4
76.0 45 165 9.9 156 10.9 148 11.8 140 13.1 132 14.4 124 15.8
84.0 50 178 10.2 169 11.2 159 12.1 151 13.4 142 14.8 134 16.1
*
Includes compressor and condenser fan motor(s).