036-21044-003-A-0304
Unitary Products 13
TABLE 2: CAPACITY RATINGS IMPERIAL
Model
Cooling Capacity
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)
1
Gas Heat Capacity
(80 / 67-95°F)
Input
(MBH)
Output
(MBH)
Temp
Rise (°F)
Gas Line
Size
(in. OD)
Cooling Cap. (MBH) Options MBH EER
090
DM 89 9.00 87
7, 14,
18, 27
- - - -
10 - - - -
120 96 15-45 3/4
15 - - - -
180 144 30-60 3/4
120
DM 116 9.0 85
14, 18,
27, 41
- - - -
15 - - - - 180 144 20-50 3/4
150
DM 138 9.0 84
14, 18,
27, 41
- - - -
15 - - - - 180 144 10-40 3/4
1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V.
TABLE 3: CAPACITY RATINGS METRIC
Model
Cooling Capacity
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)
1
Gas Heat Capacity
Input
(kW)
Output
(kW)
Temp
Rise
(°C)
Gas Line
Size
(mm. OD)
(27/19-35°C)
Cooling Cap.
(kW)
Options kW
CoP
2
090
(26.4)
DM 26.1 2.64 87
7, 14,
18, 27
- - -
10 - - - -
35.1 28.1 8.3-25 19.05
15 - - - -
52.7 42.2 17-33 19.05
120
(35.1)
DM 34.0 2.64 85
14, 18,
27, 41
- - - -
15 - - - - 52.7 42.2 11-28 19.05
150
(43.9)
DM 40.4 2.64 84
14, 18,
27, 41
- - - -
15 - - - - 52.7 42.2 5.6-22 19.05
1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V
2. CoP = Co-efficient of Performance (CoP = Cooling Capacity (kW) / Power Input (kW))