359315-YTG-B-0408
Johnson Controls Unitary Products 11
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD18S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC18
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 15.7 17.8 17.7 19.3 19.9 16.9 18.4 18.0 19.5 20.2 18.0 18.9 18.4 19.6 20.4
S.C. 16.0 13.8 12.1 12.0 9.3 17.3 15.9 13.5 13.0 9.8 18.5 17.9 14.9 13.9 10.4
KW 1.0 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
75
T.C. 15.0 16.8 16.6 18.4 19.2 16.2 17.5 17.1 18.6 19.4 17.4 18.2 17.5 18.8 19.6
S.C. 15.3 13.6 11.7 11.6 8.9 16.6 15.6 13.2 12.8 9.6 17.9 17.6 14.7 13.9 10.3
KW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
85
T.C. 14.2 15.8 15.6 17.4 18.5 15.5 16.6 16.1 17.7 18.6 16.8 17.4 16.7 18.1 18.8
S.C. 14.5 13.4 11.2 11.2 8.6 15.9 15.3 12.8 12.6 9.4 17.2 17.2 14.4 13.9 10.1
KW 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
95
T.C. 13.5 14.8 14.6 16.4 17.7 14.8 15.7 15.2 17.5 17.9 16.1 16.6 15.8 17.3 18.0
S.C. 13.8 13.1 10.8 10.7 8.2 15.2 15.0 12.5 12.4 9.1 16.6 16.9 14.2 14.0 10.0
KW 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
105
T.C. 12.6 13.7 13.2 15.1 16.5 13.8 14.6 13.8 15.5 16.7 15.0 15.5 14.4 16.0 16.8
S.C. 12.8 12.5 10.2 10.3 7.9 14.1 14.1 11.8 11.9 8.8 15.4 15.7 13.4 13.6 9.8
KW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
115
T.C. 11.6 12.6 11.8 13.8 15.4 12.7 13.5 12.5 14.2 15.5 13.8 14.5 13.1 14.6 15.6
S.C. 11.9 11.9 9.6 9.8 7.6 13.1 13.2 11.2 11.6 8.6 14.3 14.6 12.7 13.3 9.6
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
125
T.C. 10.7 11.4 10.5 12.5 14.2 11.7 12.4 11.2 12.9 14.3 12.7 13.4 11.8 13.3 14.4
S.C. 11.0 11.2 9.0 9.4 7.3 12.1 12.3 10.5 11.2 8.3 13.1 13.5 12.0 12.9 9.4
KW 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
HC18 1.00 1.00 1.00
UC18 1.00 1.00 1.00
AHP18 1.00 1.00 1.00
MV12B FC/MC18B 1.02 1.03 0.89
MA08B FC/MC18B 1.00 1.00 1.00
F4FP024 1.00 1.00 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*A12 FC/MC/PC18A 1.02 1.03 0.89
PV9*A12 FC/MC/PC18A 1.01 1.03 0.88
P(C,V)9*B12 FC/MC/PC18B 1.02 1.03 0.89
PV8*A12 HC18 1.02 1.03 0.89
PV9*A12 HC18 1.01 1.03 0.88