EasyManuals Logo
Home>York>Air Conditioner>Y34

York Y34 User Manual

York Y34
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
246653-YTG-E-0108
66 Johnson Controls Unitary Products
TABLE 51: ELECTRICAL DATA 25 TON WITH POWER EXHAUST R22
VOLTAGE
COMPRESSORS
(EACH)
OD F
AN MOTORS
(EACH)
S
UPPLY BLOWER PWR EXH MOTOR
MCA
1
(AMPS)
M
AX
FUSE
2
/
B
REAKER
3
SIZE
QTY. RLA LRA MCC QTY FLA HP FLA HP FLA
208-3-60 2 42.3 245 66.0 4 3.8
7.5 24.2
5 16.7 154 175
7.5 24.2 161 200
10 30.8 168 200
10 30.8
5 16.7 160 200
7.5 24.2 168 200
10 30.8 175 200
15 46.2
5 16.7 177 200
7.5 24.2 184 225
10 30.8 191 225
20 59.4
5 16.7 193 250
7.5 24.2 201 250
10 30.8 207 250
230-3-60 2 42.3 245 66.0 4 3.8
7.5 22.0
5 15.2 149 175
7.5 22.0 156 175
10 28.0 162 200
10 28.0
5 15.2 155 175
7.5 22.0 162 200
10 28.0 168 200
15 42.0
5 15.2 169 200
7.5 22.0 176 200
10 28.0 182 200
20 54.0
5 15.2 184 225
7.5 22.0 191 225
10 28.0 197 250
460-3-60 2 17.6 125 27.5 4 1.9
7.5 11.0
5 7.6 67 80
7.5 11.0 70 80
10 14.0 73 90
10 14.0
5 7.6 70 80
7.5 11.0 73 90
10 14.0 76 90
15 21.0
5 7.6 78 90
7.5 11.0 81 100
10 14.0 84 100
20 27.0
57.685110
7.5 11.0 89 110
10 14.0 92 110
575-3-60 2 14.2 100 22.2 4 1.5
7.5 9.0
5 6.1 54 60
7.5 9.0 57 70
10 11.0 59 70
10 11.0
5 6.1 56 70
7.5 9.0 59 70
10 11.0 61 70
15 17.0
5 6.1 63 70
7.5 9.0 65 80
10 11.0 67 80
20 22.0
5 6.1 69 90
7.5 9.0 72 90
10 11.0 74 90
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York Y34 and is the answer not in the manual?

York Y34 Specifications

General IconGeneral
BrandYork
ModelY34
CategoryAir Conditioner
LanguageEnglish

Related product manuals