JOHNSON CONTROLS
74
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m; rear to wall – 2m; control panel to end wall
– 1.2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one adjacent wall may be higher than the
unit.
NOTE: All dimensions are in mm unless specied otherwise.
Dimensions - YCAL0114 - YCAL0134 (SI)
VIEW A-A
2241
CONNECTION)
UNIT TO COOLER
60 (EDGE OF
B
435
B
(8) 13 CONDUIT K.O.'S
(2) 64,51,38 CONDUIT K.O.'S
VIEW B-B
(5) 13 CONDUIT K.O.'S
38
POWER ENTRY
127
127
321
CONTROL ENTRY
76
38
51
102
25 TYP.
98
76
229
76