EasyManuals Logo

York YCH120 User Manual

York YCH120
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
YORK INTERNATIONAL
6
2
Maximum wire size that can be accommodated by unit wiring lugs. Actual wire size must be determined based on ampacity and job
requirements using NEC wire sizing information.
ELECTRICAL DATA
POWER SUPPLY
SYSTEM NO. 1 SYSTEM NO. 2
NON-FUSED NON-FUSED
MODEL POWER
MIN.
MAX.
DISC.
INCOMING
MIN.
MAX.
DISC.
INCOMING
YCHA
CIRCUIT
DUAL
SWITCH
WIRE
CIRCUIT
DUAL
SWITCH
WIRE
AMP.
FUSE
SIZE
RANGE
2
AMP.
FUSE
SIZE
RANGE
2
VOLTS-PH-Hz
A
AV
CU/AL WIRE A
AV
CU/AL WIRE
-17 200-3-60 520 800 600 240 (1) #4-500MCM ————
-28 230-3-60 460 700 600 240 (1) #4-500MCM ————
100
-40 380-3-60 272 400 400 480 (1) #6-300MCM ————
-46 460-3-60 230 350 400 480 (1) #6-300MCM ————
-50 380/415-3-50 280 400 400 480 (1) #6-300MCM ————
-64 346-3-50 319 450 400 480 (1) #4-500MCM ————
-17 200-3-60 282 400 400 240 (1) #4-500MCM 379 600 400 240 (1) #4-500MCM
-28 230-3-60 247 350 400 240 (1) #4-500MCM 336 500 400 240 (1) #4-500MCM
120
-40 380-3-60 147 225 200 480 (1) #14-2/0AWG 198 300 200 480 (1) #14-2/0AWG
-46 460-360 125 200 200 480 (1) #14-2/0AWG 168 250 200 480 (1) #14-2/0AWG
-50 380/415-3-50 149 225 200 480 (1) #14-2/0AWG 206 300 200 480 (1) #14-2/0AWG
-64 346-3-50 162 250 200 480 (1) #6-300MCM 225 350 400 480 (1) #6-300MCM
-17 200-360 386 600 400 240 (1) #4-500MCM 386 600 400 240 (1) #4-500MCM
-28 230-3-60 343 500 400 240 (1) #4-500MCM 343 500 400 240 (1) #4-500MCM
150
-40 380-3-60 203 300 200 480 (1) #14-2/0AWG 203 300 200 480 (1) #14-2/0AWG
-46 460-3-60 172 250 200 480 (1) #14-2/0AWG 172 250 200 480 (1) #14-2/0AWG
-50 380/415-3-50 210 300 200 480 (1) #14-2/0AWG 210 300 200 480 (1) #14-2/0AWG
-64 346-3-50 230 350 400 480 (1) #6-300MCM 230 350 400 480 (1) #6-300MCM
-17 200-360 399 600 400 240 (1) #4-500MCM 517 800 600 240 (1) #4-500MCM
-28 230-3-60 353 500 400 240 (1) #4-500MCM 456 700 600 240 (1) #4-500MCM
175
-40 380-3-60 209 300 200 480 (1) #6-300MCM 272 400 400 480 (1) #6-300MCM
-46 460-3-60 177 250 200 480 (1) #6-300MCM 228 350 400 480 (1) #6-300MCM
-50 380/415-3-50 215 300 200 480 (1) #6-300MCM 277 400 400 480 (1) #6-300MCM
-64 346-3-50 235 350 400 480 (1) #4-500MCM 316 450 400 480 (1) #4-500MCM
-17 200-3-60 520 800 600 240 (1) #4-500MCM 520 800 600 240 (1) #4-500MCM
-28 230-3-60 460 700 600 240 (1) #4-500MCM 460 700 600 240 (1) #4-500MCM
200
-40 380-3-60 272 400 400 480 (1) #6-300MCM 272 400 400 480 (1) #6-300MCM
-46 460-3-60 230 350 400 480 (1) #6-300MCM 230 350 400 480 (1) #6-300MCM
-50 380/415-3-50 280 400 400 480 (1) #6-300MCM 280 400 400 480 (1) #6-300MCM
-64 346-3-50 319 450 400 480 (1) #4-500MCM 319 450 400 480 (1) #4-500MCM
MAX. DUAL
NON-FUSED
MODEL VOLTS-PH-Hz
MIN. CIR.
ELEM. FUSE
DISCONNECT INCOMING
AMPACITY
A
SWITCH WIRE RANGE
AV
-40 380-3-60 320 400 400 480
YCHA120 -46 460-3-60 271 350 400 480
-50 380/415-3-50 329 450 400 480
-40 380-3-60 370 450 400 480
YCHA150 -46 460-3-60 312 400 400 480 (1) #1/0-600MCM
-50 380/415-3-50 383 500 400 480 or
-40 380-3-60 444 600 600 480 (2) #1/0-250MCM
YCHA175 -46 460-3-60 374 500 400 480 CU/AL
-50 380/415-3-50 454 600 600 480
-40 380-3-60 494 600 600 480
YCHA200 -46 460-3-60 419 500 600 480
-50 380/415-3-50 509 700 600 480