YORK INTERNATIONAL
78
YORK INTERNATIONAL
79
FORM 150.63-EG1
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure
safety cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall 2m; rear to wall
2m; control panel to end wall 1.2m; top no obstructions allowed; distance between adjacent units 3m. No more than one
adjacent wall may be higher than the unit.
Dimensions - YCUL0016 - YCUL0026 (SI)
 
 


















MODEL YCUL A
0016 567
0026 564