628792-BTG-G-0418
Ducted Systems 9
Sound Performance
Outdoor Sound Power Levels (dB), 60 Hz
Model
Nominal
Tonnage
dB(A)
1
1
Rated in accordance with AHRI 270 Standard.
Electrical Data
Octave Bands (Hz)
63 125 250 500 1000 2000 4000 8000
YJ-30 30
92 90 93 91 89 87 83 79 74
YJ-40 40
92 90 93 91 89 87 84 80 75
YJ-50 50
93 91 94 92 90 87 84 80 75
YJ-30 thru -50 Electrical Data
Model
Compressors Outdoor Fan Motor
Minimum
Circuit
Ampacity
Maximum
Fuse Size
(A)
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
YJ-30
208/230-3-60 4 25.0 39 164 208/230-3-60 1 1/2 4 5.8 129.5 150
460-3-60 4 12.2 19 100 460-3-60 1 1/2 4 2.9 63.5 70
575-3-60 4 9.0 14 78 575-3-60 1 1/2 4 2.2 47.1 50
YJ-40
208/230-3-60 4 30.1 47 225 208/230-3-60 1 1/2 4 5.8 151.1 175
460-3-60 4 16.7 26 114 460-3-60 1 1/2 4 2.9 82.6 90
575-3-60 4 12.2 19 80 575-3-60 1 1/2 4 2.2 60.7 70
YJ-50
208/230-3-60 4 48.1 75 245 208/230-3-60 1 1/2 4 5.8 227.6 250
460-3-60 4 18.6 29 125 460-3-60 1 1/2 4 2.9 90.7 100
575-3-60 4 14.7 23 100 575-3-60 1 1/2 4 2.2 71.3 80