JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
The IP54 fan motors are the totally enclosed air-over
type with permanently lubricated double-sealed ball
bearings.
POWER AND CONTROLS PANELS
All power and controls are contained in an IP 55 cabinet
with hinged and gasket sealed outer doors.
The power panel includes:
A factory mounted non-fused disconnect switch
with external (red/yellow) lockable handle to enable
connection of the unit power supply. The disconnect
switch can be used to isolate the power for servicing
and as a emergency stop.
Factory mounted compressor contactors and
compressor fuses provide short circuit protection.
Overload protection for each compressor is provided
by inherent motor winding temperature sensing and
a trip module.
Factory mounted fan contactors and fuses provide
short circuit protection. Overload protection for
each fan is provided by a inherent motor winding
temperature device.
Factory mounted control transformer to convert the
unit supply voltage to 115 V - 1 Ø - 60 Hz for the
control system.
Control supply fuses and connections for a remote
emergency stop device.
The control panel includes:
A Liquid Crystal Display (two display lines of twenty
characters per line) with Light Emitting Diode
backlighting for easy viewing.
A Color coded 12-button keypad.
Customer terminal blocks for control inputs and liquid
ow switch.
MICROPROCESSOR CONTROLS
The microprocessor control includes:
Automatic control of compressor start/stop,
anticoincidence and anti-recycle timers, pump and
unit alarm contacts. Automatic reset to normal unit
operation after power failure.
Remote water temperature setpoint reset via an analog
input or a pulse width modulated (PWM) input signal,
or up to two steps of demand (load) limiting.
Software is loaded into the microprocessor controller
via a SD card, with programmed setpoints retained in a
lithium battery backed real time clock (RTC) memory.
Forty character liquid crystal display, with description
available in several languages.
Programmable setpoints:
Chilled liquid temperature setpoint and range
Hot liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low ambient cutout
High ambient cutout (heating only - xed)
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
Cooling suction superheat
Heating suction superheat
Displayed Data:
Leaving liquid temperature
Air coil defrost temperatures
Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
EEV output
Suction superheat
Suction temperature
Suction saturated temperature
Ambient air temperature
Metric or Imperial data
Discharge and suction pressure cutout settings
System discharge and suction pressures
Anti-recycle timer status for each system
Anti-coincident system start timer condition