FORM NO.: 6U5M-A11M-NB-EN
JOHNSON CONTROLS 8
OPERATING RANGE
Voltage Range
The maximum fluctuation range of supply voltage is ±10%
Three-phase electric phase unbalance rate should be less than 2%.
Temperature range
TABLE 1-Temperature range(YVAG012~040)
Project
012~018
020~040
Relative humidity
<90%,No lon <90%,No lon
Wire controller using the environment
temperature
-10℃~55 -10℃~55
The unit running environment
temperature range
Cooling -5℃~48℃
Heating -20℃~43℃
Cooling -5℃~48℃
Heating -25℃~43℃
Chilled water temperature range
Leaving water temperature
Cooling 5℃~25℃
Heating 30℃~52℃
Cooling 5℃~25℃
Heating 30℃~58℃
Chilled water temperature range
Enter water temperature
Cooling 10℃~30
Heating 25℃~47℃
Cooling 10℃~30
Heating 25℃~53℃
Please note that
The return water temperature control is default by the unit controller, and return water temperature
control is recommended.
The above data are obtained in the laboratory, the practical use there will be deviation affected by
the installation position and so on.
For applications with temperature below -25, please consult YORK company.
Applicable Medium
The standard design applicable medium of the unit is purified water. Please consult YORK Company for special
medium such as glycol antifreeze fluid.
Altitude
No more than 2000m
Wind side external static pressure
No more than 30Pa
Cooke Industries - Phone: +64 9 579 2185 Email: sales@cookeindustries.co.nz Web: www.cookeindustries.co.nz

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YVAG012 and is the answer not in the manual?

York YVAG012 Specifications

General IconGeneral
BrandYork
ModelYVAG012
CategoryInverter
LanguageEnglish

Related product manuals