14 Unitary Products Group
345094-YTG-D-0108
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZH03611
INDOOR COIL MODEL NO. FC/MC62D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 796 846 896
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 26.3 27.5 27.3 30.5 33.5 26.9 28.0 27.7 30.9 34.1 27.4 28.4 28.1 31.3 34.7
S.C. 26.3 23.9 20.3 20.4 16.7 26.9 25.0 20.9 21.0 17.1 27.4 26.1 21.6 21.6 17.5
K.W. 1.0 1.0 1.0 1.0 1.1 1.0 1.0 1.0 1.0 1.1 1.0 1.0 1.0 1.0 1.1
75
T.C. 25.2 26.0 25.9 28.9 32.0 25.7 26.4 26.3 29.3 32.5 26.3 26.7 26.6 29.7 33.0
S.C. 25.2 23.6 19.8 19.8 16.1 25.7 24.4 20.4 20.5 16.5 26.3 25.2 21.0 21.1 16.9
K.W. 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
85
T.C. 24.1 24.5 24.5 27.4 30.5 24.6 24.8 24.8 27.8 30.8 25.2 25.0 25.1 28.1 31.2
S.C. 24.1 23.2 19.3 19.3 15.5 24.6 23.8 19.9 19.9 15.9 25.2 24.3 20.5 20.5 16.3
K.W. 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
95
T.C. 23.0 22.9 23.0 25.9 28.9 23.5 23.1 23.3 26.2 29.2 24.0 23.4 23.6 26.5 29.5
S.C. 23.0 22.9 18.7 18.8 15.0 23.5 23.1 19.3 19.4 15.3 24.0 23.4 19.9 20.0 15.6
K.W. 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
105
T.C. 21.4 21.3 20.8 23.6 26.6 21.8 21.6 21.1 23.8 26.8 22.3 21.9 21.3 24.1 27.0
S.C. 21.4 21.3 17.9 18.0 14.2 21.8 21.6 18.4 18.6 14.5 22.3 21.9 18.9 19.2 14.9
K.W. 1.8 1.8 1.8 1.8 1.9 1.8 1.8 1.8 1.8 1.9 1.8 1.8 1.8 1.8 1.9
115
T.C. 19.8 19.7 18.7 21.3 24.3 20.2 20.1 18.9 21.5 24.5 20.6 20.4 19.1 21.8 24.7
S.C. 19.8 19.7 17.1 17.3 13.4 20.2 20.1 17.5 17.9 13.8 20.6 20.4 17.9 18.5 14.1
K.W. 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
125
T.C. 18.2 18.2 16.5 19.1 22.0 18.6 18.6 16.7 19.2 22.1 19.0 19.0 16.9 19.4 22.3
S.C. 18.2 18.2 16.4 16.5 12.6 18.6 18.6 16.6 17.1 13.0 19.0 19.0 16.9 17.7 13.4
K.W. 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
AV36 - 0.98 0.97 0.97
AV/SV48 - 1.01 1.04 0.98
MV16C FC/MC43C 0.97 0.93 0.95
MV16C FC/MC48C 0.98 0.95 0.96
MV12D FC/MC48D 0.97 0.91 0.96
MV12D FC/MC60D 0.97 0.93 0.97
Variable Speed
Furnace
Coil
T.C. S.C. KW
P(C,V)8*B16 FC/MC/PC43B 0.96 0.92 0.95
P(C,V)8*C16 FC/MC/PC43C 0.93 0.84 0.94
P(C,V)8*C20 FC/MC/PC43C 0.96 0.93 0.94
P(C,V)9*B12 FC/MC/PC43B 0.96 0.93 0.94
P(C,V)9*C16 FC/MC/PC43C 0.97 0.93 0.97
P(C,V)9*C20 FC/MC/PC43C 0.97 0.94 0.95
P(C,V)8*C16 FC/MC/PC48C 0.94 0.86 0.95
P(C,V)8*C20 FC/MC/PC48C 0.97 0.94 0.95
P(C,V)9*C16 FC/MC/PC48C 0.98 0.94 0.97
P(C,V)9*C20 FC/MC/PC48C 0.98 0.95 0.95
P(C,V)9*D20 FC/MC/PC48D 0.98 0.95 0.96
P(C,V)8*C16 FC/PC60C 0.95 0.87 0.96
P(C,V)8*C20 FC/PC60C 0.98 0.96 0.96
P(C,V)9*C16 FC/PC60C 0.98 0.95 0.97
P(C,V)9*C20 FC/PC60C 0.98 0.96 0.96
P(C,V)9*D20 FC/MC/PC60D 0.97 0.95 0.96
P(C,V)8*C20 FC/MC62D 0.97 0.94 0.96
P(C,V)9*C20 FC/MC62D 0.98 0.95 0.96
P(C,V)9*D20 FC/MC62D 0.98 0.95 0.96
P(C,V)8*C16 HC42 0.93 0.85 0.94
P(C,V)8*C20 HC42 0.96 0.93 0.95
P(C,V)9*C16 HC42 0.97 0.93 0.97
P(C,V)9*C20 HC42 0.98 0.94 0.95