EasyManuals Logo
Home>York>Heat Pump>YZH024 THRU 060

York YZH024 THRU 060 User Manual

York YZH024 THRU 060
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
2 Unitary Products Group
345094-YTG-D-0108
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data
MODEL
YZH02411 YZH03611 YZH04811 YZH06011
Unit Supply Voltage 208-230V, 1φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 18.2 23.6 29.2 34.8
Max. Overcurrent Device Amps
2
30 40 50 60
Min. Overcurrent Device Amps
3
20 25 30 35
Multi-stage Compressor Yes Yes Yes Yes
Compressor Type Scroll Scroll Scroll Scroll
Compressor Amps
Rated Load 12.3 16.6 21.1 25.6
Locked Rotor 52 82 96 118
Crankcase Heater No No No No
Fan Motor Amps Rated Load 2.8 2.8 2.8 2.8
Fan Diameter Inches 24 24 24 24
Fan Motor
Rated HP 1/3 1/3 1/3 1/3
Nominal RPM 685 685 685 685
Nominal CFM 2,940 2,666 3,376 3,332
Coil
Face Area Sq. Ft. 23.58 23.58 23.58 23.58
Rows Deep 2222
Fins / Inch 16 16 14 14
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
14 - 12 12 - 7 12 - 13 14 - 8
Charge Per Foot, Oz. 0.62 0.62 0.67 0.67
Operating Weight Lbs. 275 275 280 315
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection .
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
VAPOR
LIQUID
2-3/8
3-1/8
6-1/2
C
A
B
Unit
Model
Dimensions
(Inches)
Refrigerant
Connection
Service Valve Size
A B C Liquid Vapor
024 39-1/2 42 34
3/8”
3/4”
036 39-1/2 42 34
048 39-1/2 42 34
7/8”
060 39-1/2 42 34