26 OI/266/HART-EN Rev. M | 2600T Series Pressure transmitters
5 Mounting
5.14.3 Liquid level measurements on closed tanks
and non condensable fluids (dry leg)
Mount the transmitter at the same height or below the
lowest level to be measured.
Connect the + (H) side of the transmitter to the bottom of
the tank.
Connect the - (L) side of the transmitter to the upper part
of the tank, above the maximum level of the tank.
5.14.4 Liquid level measurement with closed tanks and
condensable fluids (wet leg)
Mount the transmitter at the same height or below the
lowest level to be measured.
Connect the + (H) side of the transmitter to the bottom of
the tank.
Connect the - (L) side of the transmitter to the upper part
of the tank.
Fill the vertical section of the connecting line to the upper
part of the tank with a compatible liquid through the
dedicated filling tee.
Figure 33: Level measurement on closed tank with dry leg
Figure 34: Level measurement on closed tank with wet leg
5.14.5 Liquid level measurement with open tanks
Mount the transmitter at the same height or below the
lowest level to be measured.
Connect the + (H) side to the bottom of the tank.
Vent the “–” (L) side of the transmitter to the atmosphere
(in this case a gauge pressure is shown; the (L) side is
already vented to the atmosphere).
Figure 35: Level measurement on open tank with P style transmitter