7.8
.
1.7
-
1
Page
13
3
.
BUILT
-
IN
TEST
FEATURE
Tests
should
be
made
on
a
de
-
energized
main
circuit
,
energized
circuit
,
be
sure
to
take
all
necessary
precautions
,
available
to
make
this
test
.
If
tests
must
be
made
on
an
Control
power
must
be
The
built
-
in
test
is
provided
as
a
convenient
functional
test
of
the
relay
and
assoc
-
iated
trip
circuit
.
The
test
function
works
as
follows
:
when
you
depress
the
button
labelled
TRIP
,
the
pickup
circuit
of
the
relay
is
actuated
.
The
relay
then
times
out
and
the
output
contacts
transfer
to
trip
the
associated
breaker
or
auxiliary
relay
,
The
test
button
must
be
held
down
continuously
for
the
time
set
on
the
relay
in
order
to
obtain
an
operation
.
The
pickup
led
and
the
target
is
displayed
,
operating
should
light
during
this
period
,
indicating
timing
is
underway
.
Catalog
Series
237
P
/
237
F
/
437
P
/
437
F
4
.
ACCEPTANCE
TESTS
Without
Phase
-
Shifting
Source
:
A
typical
acceptance
test
circuit
is
given
in
Figure
8
.
The
control
voltage
source
should
match
the
relay
s
front
panel
rating
.
On
dual
-
rated
units
be
sure
the
internal
selector
link
has
been
positioned
properly
.
The
ac
source
should
be
60
Hz
.
or
50
Hz
.
to
match
relay
s
rating
,
and
the
voltage
and
current
outputs
must
be
essentially
in
phase
.
a
.
Set
the
PICKUP
dial
to
0.1
ampere
and
the
TIME
dial
to
1
second
.
b
.
Apply
control
voltage
.
Depress
the
TARGET
RESET
button
.
The
target
should
reset
to
black
.
Apply
approximately
120
vac
to
the
voltage
input
.
c
.
Apply
the
current
signal
and
increase
until
the
pickup
light
comes
on
solidly
and
the
contacts
transfer
.
(
The
pickup
light
may
blink
near
pickup
.
)
target
should
set
to
orange
when
the
output
contacts
transfer
,
the
operating
point
should
be
between
0.07
and
0.13
amperes
.
The
Current
at
d
.
Increase
the
input
current
to
0.5
ampere
.
Start
the
test
set
.
between
0.9
and
1.1
seconds
.
Turn
off
the
test
source
and
reset
The
relay
should
operate
to
stop
the
timer
the
timer
.
e
.
Reverse
the
current
leads
at
terminals
1
and
2
of
the
relay
,
target
.
The
relay
should
not
pick
up
.
Reset
the
Apply
voltage
and
current
and
increase
the
current
signal
to
1
amp
.
If
the
actual
settings
to
be
used
in
the
application
are
known
,
the
relay
should
be
calibrated
by
repeating
steps
(
c
)
and
(
d
)
,
except
adjusting
the
relay
dials
until
the
desired
pickup
current
and
time
delay
are
obtained
.
Timing
tests
should
be
run
with
the
current
set
at
150
%
of
pickup
or
higher
.
f
.
With
Phase
-
Shifting
Source
:
If
a
test
set
with
the
ability
to
shift
the
phase
of
the
ac
input
current
and
voltage
is
being
used
,
a
check
of
the
operating
characteristic
can
be
made
in
place
of
test
(
e
)
above
.
A
typical
test
circuit
is
shown
in
Fig
.
9
.
First
perform
the
tests
(
b
)
,
(
c
)
,
and
(
d
)
given
above
,
current
source
also
at
0
deg
)
.
(
Set
test
set
voltage
source
for
120
vac
at
0
degrees
,
Then
determine
the
operating
characteristic
:
a
.
Set
the
relay
s
pickup
at
0.1
ampere
and
the
time
delay
at
1
second
.
relay
is
equipped
with
a
maximum
torque
angle
selector
plug
(
see
Figure
7
)
place
the
plug
in
the
30
°
position
for
this
test
.
If
the
b
.
For
the
standard
Type
32
R
(
catalog
237
xxxx
1
or
437
xxxx
1
)
,
set
the
phase
angle
of
the
voltage
source
on
the
test
set
to
120
v
at
30
°
lead
.
Set
the
current
source
on
the
test
set
to
1
ampere
.
Vary
the
phase
of
the
current
signal
.
The
relay
should
pick
up
and
trip
for
phase
angles
from
90
°
lead
through
0
°
to
90
°
lag
.
The
relay
should
not
operate
for
phase
angles
from
90
°
lag
through
180
°
to
90
°
lead
.
The
tolerance
on
the
operating
characteristic
is
+
/
-
6
degrees
.
for
relays
without
the
30
°
internal
shift
(
catalog
237
xxxx
2
or
437
xxxx
2
)
,
or
for
the
0
°
position
of
the
maximum
torque
angle
selector
plug
(
see
Fig
5
)
set
the
voltage
source
at
120
v
,
0
°
.
Note
:
Courtesy of NationalSwitchgear.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CIRCUIT SHIELD 437W Series and is the answer not in the manual?

ABB CIRCUIT SHIELD 437W Series Specifications

General IconGeneral
BrandABB
ModelCIRCUIT SHIELD 437W Series
CategoryRelays
LanguageEnglish

Related product manuals