INTRODUCTION
These
instructions
contain
the
information
required
to
properly
install
,
operate
,
and
test
the
ABB
Circuit
-
Shield
Type
32
R
Reverse
Power
Relay
,
catalog
series
237
P
,
437
P
,
237
F
,
437
F
,
437
W
,
and
437
G
.
The
relay
is
housed
in
a
case
suitable
for
conventional
semiflush
panel
mounting
.
All
connections
to
the
relay
are
made
at
the
rear
of
the
case
and
are
clearly
numbered
.
The
437
series
relays
provide
totally
drawout
construction
with
integral
test
facilities
.
Current
transformer
shorting
is
accomplished
by
a
direct
-
acting
spring
and
blade
assembly
upon
removal
of
the
relay
from
its
case
.
Sequenced
disconnects
prevent
nuisance
tripping
during
withdrawal
or
insertion
of
the
relay
if
the
normally
closed
contact
is
used
in
the
application
.
The
237
series
relays
are
of
partial
drawout
construction
,
with
the
input
transformers
remaining
in
the
case
upon
withdrawal
of
the
lower
circuit
board
.
Most
settings
are
made
on
the
front
panel
of
the
relay
,
behind
a
removable
clear
plastic
cover
.
The
target
is
reset
by
means
of
a
pushbutton
extending
through
the
cover
.
PRECAUTIONS
The
following
precautions
should
be
taken
when
applying
these
relays
.
Be
sure
wiring
agrees
with
the
connection
Incorrect
wiring
may
result
in
damage
,
diagram
for
the
particular
relay
before
energizing
.
1
.
Apply
only
the
rated
voltage
marked
on
the
relay
front
panel
.
For
units
rated
for
2
.
use
with
dc
control
power
,
the
proper
polarity
must
be
observed
.
For
units
with
dual
-
rated
control
voltage
,
the
control
voltage
selector
plug
located
on
the
lower
circuit
board
must
be
placed
in
the
correct
position
for
the
system
control
voltage
.
boards
must
be
separated
to
gain
access
to
the
plug
.
3
.
On
earlier
437
series
units
the
upper
and
lower
circuit
4
.
For
catalog
series
237
units
,
16
to
terminal
G
.
a
shorting
link
or
jumper
is
required
from
terminal
This
is
not
used
on
series
437
units
.
Do
not
use
excessive
force
.
Drawout
elements
should
insert
in
the
case
smoothly
.
5
.
6
.
High
voltage
insulation
tests
are
not
recommended
.
A
high
-
pot
test
was
performed
on
the
relay
at
the
factory
.
See
section
on
Testing
for
additional
information
.
Follow
test
instructions
to
verify
that
the
relay
is
in
proper
working
order
.
7
.
Caution
:
since
troubleshooting
entails
working
with
energized
equipment
,
care
should
be
taken
to
avoid
personal
shock
.
Only
competant
technicians
familiar
with
good
safety
practices
should
service
these
devices
.
PLACING
THE
RELAY
INTO
SERVICE
1
.
RECEIVING
.
HANDLING
.
STORAGE
Upon
receipt
of
the
relay
(
when
not
included
as
part
of
a
switchboard
)
examine
for
shipping
damage
.
notify
your
ABB
representative
or
the
factory
.
Use
normal
care
in
handling
to
avoid
mechanical
damage
.
Keep
clean
and
dry
.
If
damage
or
loss
is
evident
,
file
a
claim
at
once
and
promptly
Courtesy of NationalSwitchgear.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CIRCUIT SHIELD 437W Series and is the answer not in the manual?

ABB CIRCUIT SHIELD 437W Series Specifications

General IconGeneral
BrandABB
ModelCIRCUIT SHIELD 437W Series
CategoryRelays
LanguageEnglish

Related product manuals