Time
Delay
:
The
437
W
/
437
G
series
is
provided
with
a
time
delay
on
pickup
.
An
internal
link
must
be
positioned
to
set
the
timing
function
for
a
definite
-
time
characteristic
or
for
an
inverse
characteristic
.
The
definite
delay
on
standard
units
is
continuously
adjus
-
The
inverse
characteristic
curve
is
shown
in
Figure
6
.
table
from
1
to
30
seconds
.
Relays
with
non
-
standard
delays
will
be
marked
appropriately
.
The
time
delay
should
be
set
to
the
time
needed
to
prevent
nuisance
operations
due
to
temporary
self
-
correcting
power
reversals
.
A
setting
of
10
-
15
seconds
is
typical
.
4
.
INDICATORS
LED
Pickup
Indicator
:
A
1
ight
-
emitting
-
diode
pickup
indicator
is
provided
to
assist
in
testing
and
to
provide
operating
personnel
with
information
on
the
status
of
the
relay
.
This
can
be
especially
helpful
when
placing
the
relay
into
service
and
making
initial
settings
.
The
relay
s
timer
will
be
timing
when
this
indicator
lights
,
and
if
the
condition
persists
,
the
relay
will
operate
.
If
the
indicator
is
flashing
on
and
off
,
system
conditions
are
near
the
relay
s
operating
threshold
,
however
,
the
timer
is
reset
whenever
the
led
goes
out
,
and
a
relay
operation
will
not
occur
.
Target
Indicator
:
When
the
relay
s
output
contacts
transfer
to
trip
the
breaker
,
the
target
indicator
is
signalled
electronically
to
set
and
display
orange
.
The
target
retains
indication
even
on
loss
of
control
voltage
,
and
must
be
reset
manually
.
In
order
to
reset
the
target
,
control
power
must
be
present
and
the
inputs
to
the
relay
below
pickup
.
APPLICATION
DATA
The
most
common
application
for
ABB
Type
32
R
relays
is
the
reverse
power
(
anti
-
motoring
)
protection
of
a
generator
and
its
prime
-
mover
.
The
maginitude
of
power
required
to
motor
the
generator
varies
widely
depending
on
the
type
of
prime
mover
(
diesel
,
gas
turbine
,
etc
.
)
These
relays
provide
wide
sensitivity
ranges
and
high
continuous
ratings
to
allow
full
use
of
the
sensitivity
.
Only
one
single
-
phase
relay
is
required
in
this
application
,
as
the
reverse
power
will
be
essentially
equal
in
all
phases
.
A
relay
setting
of
20
-
50
%
of
the
power
required
to
motor
the
particular
machine
being
protected
is
suggested
,
override
temporary
self
-
correcting
power
synchronizing
,
should
be
set
.
A
time
delay
sufficient
to
reversals
,
such
as
occur
during
A
typical
setting
would
be
15
seconds
.
Catalog
Series
237
P
/
237
F
/
437
P
/
437
F
:
Relays
in
this
series
are
current
-
directional
relays
,
rather
than
true
power
measurement
types
.
The
operating
characteristic
is
shown
in
Figure
5
.
An
advantage
of
this
type
of
unit
is
that
its
sensitivity
to
current
magnitude
and
direction
does
not
change
with
the
magnitude
of
polarization
voltage
.
Although
the
normal
polarization
voltage
to
the
relay
is
120
vac
,
the
relay
will
be
fully
polarized
at
voltages
down
below
10
volts
.
An
internal
phase
-
shift
circuit
provides
the
30
degree
shift
required
so
the
line
-
to
-
line
polarization
voltage
can
be
properly
compared
in
phase
to
the
line
current
.
(
If
the
phase
A
-
to
-
neutral
voltage
is
used
,
the
internal
phase
-
shift
link
should
be
set
to
0
°
,
rather
than
30
°
.
)
For
unity
power
factor
conditions
,
the
three
-
phase
kilowatts
to
cause
relay
operation
can
be
estimated
by
the
following
calculation
:
/
3
*
V
*
I
*
N
where
KW
V
=
system
line
to
line
voltage
in
kilovolts
.
I
=
relay
pickup
setting
in
amperes
.
CT
ratio
.
N
An
adjustable
definite
-
time
delay
characteristic
with
a
range
of
1
to
30
seconds
is
provided
on
standard
units
.
For
unusual
applications
,
special
time
ranges
including
instantaneous
operation
can
be
provided
.
Contact
the
factory
.
Reverse
VAR
Detection
:
If
this
model
is
connected
as
shown
in
Figure
4
,
and
set
-
up
with
an
internal
0
°
phase
-
shift
,
it
becomes
a
reverse
var
detector
,
used
for
loss
-
of
-
field
protection
in
installations
where
the
cost
of
an
impedance
type
relay
,
such
as
the
ABB
Type
40
,
can
not
be
justified
,
application
.
Catalog
series
437
W
/
437
G
units
are
now
preferred
for
this
Courtesy of NationalSwitchgear.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CIRCUIT SHIELD 437W Series and is the answer not in the manual?

ABB CIRCUIT SHIELD 437W Series Specifications

General IconGeneral
BrandABB
ModelCIRCUIT SHIELD 437W Series
CategoryRelays
LanguageEnglish

Related product manuals