- 16 -
000400BG
2 - Characteristics
Characteristics and technical data
Table: Technical Data PVI-3.0-TL-OUTD PVI-3.6-TL-OUTD PVI-4.2-TL-OUTD
Input
Absolute Maximum Input Voltage (Vmax,abs) 600 V
Rated Input Voltage (Vdcr) 360 V
Input start-up voltage (Vstart) 200 V (adj. 120...350 V)
Input operating interval (Vdcmin...Vdcmax) 0.7 x Vstart...
580
V
Input Nominal Power(Pdcr) 3120 Wp 3750 Wp 4375 W
Number of Independent MPPT 2
Maximum input power for Each MPPT
(PMPPTmax)
2000 W 3000 W 3000 W
Input voltage interval (VMPPTmin ... VMPPTmax)
to Pacr (parallel MPPT conguration)
160…530 V 120...530 V 140...530 V
DC Power limiting for each MPPT
with Independent MPPT Conguration to Pacr,
maximum unbalance example
2000 W
[200V≤VMPPT≤530V]
other channel:
Pdcr-2000W
[112V≤VMPPT≤530V]
3000 W
[190V≤VMPPT≤530V]
other channel:
Pdcr-3000W
[90V≤VMPPT≤530V]
3000 W
[190V≤VMPPT≤530V]
other channel:
Pdcr-3000W
[90V≤VMPPT≤530V]
Maximum DC Input Current (Idcmax) / for each
MPPT (IMPPTmax)
20.0 A / 10.0 A 32.0 A / 16.0 A 32.0 A / 16.0 A
Maximum Return current (AC side vs DC side) Negligible
Number of DC Connection Pairs in Input for
each MPPT
1 pair
DC Input Connector type (components indicated
or equivalents)
Quick Fit PV Connector
(4)
Type of photovoltaic panels that can be con-
nected at input according to IEC 61730
Class A
Input protection
Reverse Polarity Protection Yes, from current limited source
Input Overvoltage protection for each MPPT -
Varistors
2
Maximum short-circuit current for each MPPT 12.5 A 20.0 A 20.0 A
Insulation Check Complying with the local standard
DC Disconnect Switch rating ( -S Version) Max. 25 A / 600 V
Output
AC Connection to the grid Monophase
Nominal AC output voltage (Vacr) 230 V
Output voltage range (Vacmin...Vacmin) 180...264 V
(1)
Nominal AC Output Power (Pacr @cosφ=1) 3000 W 3600 W 4200 W
Maximum apparent Output power (Smax) 3330 VA 4000 VA 4670 VA
Maximum output current (Iacmax) 14.5 A 17.2 A
(2)
20.0 A
Contribution to short-circuit current 16.0 A 19.0 A 22.0 A
Inrush current Negligible
Maximum fault current <25 A rms (100ms)
Rated Output Frequency (fr) 50 Hz / 60 Hz
Output Frequency Range (fmin...fmax) 47...53 Hz / 57…63 Hz
(3)
Nominal Power Factor
> 0.995, adj. ± 0.9 with
Pacr =3.0 kW
> 0.995, adj. ± 0.9 with
Pacr =3.6 kW
> 0.995, adj. ± 0.9 with
Pacr =4.2 kW
Total Current Harmonic Distortion < 3.5%
AC Connections Type Screw terminal block (max cross-section 16 mm
2
); cable gland M25
Output protection
Anti-islanding Protection Complying with the local standard
Maximum AC Overcurrent external protection 16.0 A 19.0 A 22.0 A
Output overvoltage protection - Varistors 2 (L - N / L - PE)

Other manuals for ABB PVI-3.0-TL-OUTD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVI-3.0-TL-OUTD and is the answer not in the manual?

ABB PVI-3.0-TL-OUTD Specifications

General IconGeneral
BrandABB
ModelPVI-3.0-TL-OUTD
CategoryInverter
LanguageEnglish

Related product manuals