EasyManuals Logo
Home>ABB>Protection Device>REF630

ABB REF630 User Manual

ABB REF630
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Table 36. Transient/intermittent earth-fault protection (INTRPTEF) main settings
Parameter Function Value (Range) Step
Directional mode INTRPTEF 1=Non-directional
2=Forward
3=Reverse
-
Operate delay time INTRPTEF 0.04...1200.00 s 0.01
Voltage start value
(voltage start value
for transient EF)
INTRPTEF 0.005...0.500 pu 0.001
Operation mode INTRPTEF 1=Intermittent EF
2=Transient EF
-
Peak counter limit
(Min requirement for
peak counter before
start in IEF mode)
INTRPTEF 2...20 1
Table 37. Negative phase-sequence overcurrent protection (NSPTOC)
Characteristic
Value
Operation accuracy At the frequency f = f
n
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
I
Fault
= 2 × set Start
value
I
Fault
= 10 × set Start
value
Typical 23 ms (±15 ms)
Typical 16 ms (±15 ms)
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics DFT: -50dB at f = n × f
n
, where n = 2, 3, 4, 5,
1)
Operate curve type
= IEC definite time, negative sequence current before fault = 0.0, f
n
= 50Hz
2) Includes the delay of the signal output contact
3)
Maximum Start value = 2.5 × I
n
, Start value multiples in range of 1.5 to 20
Feeder Protection and Control 1MRS756380 A
REF630
Product version: 1.0 Issued: 15.09.2009
34 ABB

Table of Contents

Other manuals for ABB REF630

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF630 and is the answer not in the manual?

ABB REF630 Specifications

General IconGeneral
BrandABB
ModelREF630
CategoryProtection Device
LanguageEnglish

Related product manuals