EasyManuals Logo
Home>ABB>Protection Device>REF630

ABB REF630 User Manual

ABB REF630
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
Table 97. Fuse failure supervision (SEQRFUF)
Characteristic Value
Operation accuracy At the frequency f = f
n
Current: ±1.5% of the set value or ±0.002 × I
n
Voltage: ±1.5% of the set value or ±0.002 × U
n
Operate time
1)
NPS function
U
Fault
= 1.1 x set Neg
Seq voltage Lev
Typical 35 ms (±15
ms)
U
Fault
= 5.0 x set Neg
Seq voltage Lev
Typical 25 ms (±15
ms)
Delta function
ΔU = 1.1 x set
Voltage change rate
Typical 35 ms (±15
ms)
ΔU = 2.0 x set
Voltage change rate
Typical 28 ms (±15
ms)
1) Includes the delay of the signal output contact, f
n
= 50 Hz, fault voltage with nominal frequency injected from
random phase angle
Table 98. Station battery supervision (SPVNZBAT)
Characteristic
Value
Operation accuracy ±1.0% of the set value
Operate time accuracy ±1.0% of the set value or ±40 ms
Feeder Protection and Control 1MRS756380 A
REF630
Product version: 1.0 Issued: 15.09.2009
60 ABB

Table of Contents

Other manuals for ABB REF630

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF630 and is the answer not in the manual?

ABB REF630 Specifications

General IconGeneral
BrandABB
ModelREF630
CategoryProtection Device
LanguageEnglish

Related product manuals