22
Event codes
When the capacitor bank protection module
SPCJ 4D40 is linked to a control data commu-
nicator over the SPA bus, the module will pro-
vide time stamped event markings e.g. to a
printer. The events are printed out in the for-
mat: time, user specified text and an event code.
The events are generated on starts, trips, resett-
ings and output relay operations. Every func-
tion has their own code designation from E1...
E34.
Masking parameters can be used to inhibit event
generations from one or several functions.
Code Event Number Default value
representing of the factor
the event
E1 Starting of stage I
b
>10
E2 Starting of stage I
b
> reset 2 0
E3 Tripping of stage I
b
>44
E4 Tripping of stage I
b
> reset 8 0
E5 Starting of stage I
a
>160
E6 Starting of stage I
a
> reset 32 0
E7 Tripping of stage I
a
>6464
E8 Tripping of stage I
a
> reset 128 0
Default checksum for mask V155 68
E9 Starting of stage I< 1 0
E10 Starting of stage I< reset 2 0
E11 Tripping of stage I< 4 4
E12 Tripping of stage I< reset 8 0
E13 Starting of stage I
1
>160
E14 Starting of stage I
1
> reset 32 0
E15 Tripping of stage I
1
>6464
E16 Tripping of stage I
1
> reset 128 0
Default checksum for mask V156 68
E17 Starting of stage I
2
>10
E18 Starting of stage I
2
> reset 2 0
E19 Tripping of stage I
2
>44
E20 Tripping of stage I
2
> reset 8 0
E21 Beginning of external trip signal 16 16
E22 External trip signal reset 32 0
E23 Beginning of reconnection inhibit 64 0
E24 End of reconnection inhibit 128 0
Default checksum for mask V157 20
An event buffer is capable to memorize up to
eight events. If more than eight events occure
before the content of the buffer is send to the
communicator an overflow event "E51" is gen-
erated. This event has to be resetted by writing
a command "0" to parameter C over the SPA-
bus.
More information about the serial communi-
cation over the SPA-bus can be found in the
pamphlet "SPA-BUS COMMUNICATION
PROTOCOL", 34 SPACOM 2 EN1.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SPAJ 160 C and is the answer not in the manual?

ABB SPAJ 160 C Specifications

General IconGeneral
BrandABB
ModelSPAJ 160 C
CategoryRelays
LanguageEnglish

Related product manuals