12
IFCLITY1106 - 5773010_01
FCLI 4-pipe versions FCLI 34 44 64 124
Heating
Heating output 70°C
Speed 4 W - 3070 3800 12500
Speed 3 W 2600 2730 3380 10400
Speed 2 W 2190 2290 2990 9300
Speed 1 W 1950 1960 2640 7050
Water fl ow rate
Speed 4 l/h - 264 327 1075
Speed 3 l/h 224 235 291 894
Speed 2 l/h 188 197 257 800
Speed 1 l/h 168 169 227 606
Pressure drop (VL)
Speed 4 kPa - 14 21 29
Speed 3 kPa 11 12 17 21
Speed 2 kPa 8 8 14 17
Speed 1 kPa 6 6 11 10
Cooling
Cooling capacity
Speed 4 W - 3650 4610 8800
Speed 3 W 1900 3000 3640 7270
Speed 2 W 1470 2340 2970 6220
Speed 1 W 1160 1810 2460 4570
Sensible cooling capacity
Speed 4 W - 2920 3530 6770
Speed 3 W 1520 2180 2600 5520
Speed 2 W 1250 1680 2100 4670
Speed 1 W 990 1270 1720 3370
Water fl ow rate
Speed 4 l/h - 628 793 1514
Speed 3 l/h 327 516 626 1250
Speed 2 l/h 253 402 511 1070
Speed 1 l/h 200 311 423 786
Pressure drop (VL)
Speed 4 kPa - 22 31 38
Speed 3 kPa 10 15 21 27
Speed 2 kPa 7 10 14 20
Speed 1 kPa 4 6 10 12
Common data
Fans no. 1 1 1 1
Air fl ow rate
Speed 4
cu.m/h
- 700 880 1750
Speed 3
cu.m/h
600 530 660 1350
Speed 2
cu.m/h
410 360 500 1100
Speed 1
cu.m/h
300 260 380 750
Sound power
Speed 4 dB(A) - 53 61 60
Speed 3 dB(A) 46 46 54 54
Speed 2 dB(A) 38 38 47 50
Speed 1 dB(A) 35 35 41 44
Sound pressure
Speed 4 dB(A) - 44 52 51
Speed 3 dB(A) 37 37 45 45
Speed 2 dB(A) 29 29 38 41
Speed 1 dB(A) 26 26 32 35
Input power
Speed 4 W - 75 83 175
Speed 3 W 45 47 53 125
Speed 2 W 31 32 37 105
Speed 1 W 21 22 26 55
Input current (max speed) A 0.22 0.33 0.37 0.75
Starting current A 0.66 0.99 1.11 2.25
Power supply V / Hz 230 ~ 50Hz
Maximum protection level IP 20 20 20 20
Heat exchanger water content L 1.2 1.5 2.1 4.5
Water connections (cold circuit) Ø gas 3/4” 3/4” 3/4” 3/4”
Water connections (hot circuit) Ø gas 1/2” 1/2” 1/2” 1/2”
Kvs (3-way valve, standard version) 2.5 2.5 2.5 4
Kvs (2-way valve, V2 version) 2.5 2.5 2.5 2.5
Level of sound pressure (A-weighted) measured in the room with
volume V = 100 m
3
, reverberation time t = 0.5 s; direction factor
Q = 2; distance r = 2.5m
Cooling:
• External air temperature 27°C D.B. ; 19°C W.B.
Water inlet temperature 7°C ; t water 5°K
Heating 50°C:
• External air temperature 20°C
Water inlet temperature: 50°C; t water 10°K
Heating 70°C:
• External air temperature 20°C
Water inlet temperature: 50°C; t water 10°K
The leakage current to earth of several
devices placed under the same circuit
breaker is summed, so attention should be
paid to the calibration of the circuit breaker
and possibly consider the division of the
installation into several circuits each of
which protected by its own circuit breaker.
TECHNICAL DATA
= Performance certified EUROVENT 6/3 - Sound tests certified EUROVENT 8/2 (ISO 3741/2001)
Performance values refer to the following conditions: