4.5. Problems during the test setup wizard
turns off
1. Increase the pressure adjust
oven stays on at the minimum. ( see section 4.3.1.)
2. Verify type of gas and inlet gas pressure.
3. Check gas nozzle.
4. Check the gas pipe fixing.
5. Check the wiring of the flame sensor.
6. Check that the outlet pressure of the gas is free.
7. Clean the blower fan air intake.
8. Increase the blower fan speed at minimum (see
section 4.3.2.)
“break away”
burner.
1. Check gas nozzle.
2. Verify type of gas and inlet gas pressure.
3.
Measure the CO and CO2 values and compare them
with min/max value in the table. (see chapter 4.2.)
ALARM E27:
Gas test missed
Check that the chamber temperature has not exceeded 200
°C in which case do a cool
down, and then rerun the test.
Check that the 10 minutes timeout is not expires.
In case of other alarms see “GAS ALARM TABLE”
Important: At the end of each intervention on the gas system must perform the
procedure for testing gas by measuring the CO and CO2, and verify that the data
is within the fields declared by the manufacturer.