ASSEMBLY
PAGE2 REV. 01 2012-MAR-22
ANSUL Fire Suppression/Securing Systems
Operation and Maintenance – Model 100/30
f. Secure fill cap and hand tighten. (Make certain gasket is in
place before reinstalling fill cap.)
NOTICE
If the fill cap is an indicator model, be
sure the red indicator stem is in the
DOWN POSITION before securing fill
cap.
5. Confirm nitrogen cylinder is secure in retaining brackets.
Remove safety shipping cap from cylinder, and make certain
that pointer on pressure gauge is in the BLACK operating
range. (Retain shipping cap for future use.)
6. Remove safety plug from nitrogen cylinder valve. (Retain plug
for future use.)
Do not place body or head in front of cylinder valve outlet. If
valve is accidentally operated, velocity of unrestricted
escaping gas is forceful enough to cause injury, especially
about the face and head.
7. Connect high pressure hose to nitrogen cylinder valve and
wrench tighten.
Do not strike “pull” lever when connecting hose to cylinder
valve. Escaping gas is forceful enough to cause injury.
8. Make certain visual inspection seals on nitrogen cylinder valve
are still intact. Replace any broken or missing visual inspec-
tion seals (Part No. 197).
9. Make certain dry chemical tank valve handles are ring pinned
and sealed in the operating position:
BLUE Hose Clean-Out Valve . . . . . . . . . . . . . . . . . . . . Closed
BLACK Dry Chemical Valve . . . . . . . . . . . . . . . . . . . . . . Open
10. Replace any broken or missing visual inspection seals (Part
No. 15999).
11. Make certain ANSULITE AFFF solution tank valve handles are
ring pinned and sealed in the operating position:
BLUE Hose Clean-Out Valve . . . . . . . . . . . . . . . . . . . . Closed
BLACK AFFF Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open
12. Replace any broken or missing visual inspection seals (Part
No. 15999).
13. To give maximum assurance that the system will operate
effectively and safetly, a maintenance examination could be
performed at this time. Instruct personnel in operation of the
fire suppress ing/secur ing system.
14. Record date of placement in service.
!
WARNING
!
WARNING