BECKHOFF Drive Technology 5 Installation
AX5000 Version 6.2 35
5.2.1 Mains supply connection (X01)
The servo drives of the AX5000 series are equipped with a wide voltage input "X01" and can
be connected to voltage systems between single-phase 100 V
AC -10%
- 240 V
AC +10%
and
three-phase 100 V
AC -10%
- 480 V
AC +10%
.
Note
Connection to the standard mains supply (TT/TN) with earthed centre is
described below. Details for connections to other supply systems (e.g. IT-
mains supply, isolating transformer etc.) can be found in the “AX5000 User
manual” on the enclosed CD
or can be downloaded from our website at
single-phase 100
-10%
- 240
+10%
V
AC
three-phase 100
-10%
- 480
+10%
V
AC
5.2.1.1 External protection for individual devices, CE-compliant
CAUTION
Fire hazard through short circuit!
• The following data refer to individual devices. Please note the total
current of all connected devices in a multi-axis system.
• The recommended fuses are designed for line protection. The servo
drives feature integrated self-protection.
Single-phase
*) Application class "gG" mains fuses according to IEC 60269 with characteristic “T” or
"C" type automatic circuit breakers must be used.
Three-phase
*) Application class "gG" mains fuses according to IEC 60269 with characteristic “T” or
"C" type automatic circuit breakers must be used.
5.2.1.2 Internal protection, CE-compliant
24 V - peripheral voltage