5 Installation BECKHOFF Drive Technology
36 Version 6.2 AX5000
5.2.1.3 External protection, UL-compliant
Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the Manufacture Instructions, National
Electrical Code and any additional local codes.
Suitable for use on a circuit capable of delivering not more than 18000 rms symmetrical
amperes, 480 V maximum, when protected by RK5 class fuses.
Single-phase
Fusing
AX5101
AX5103
AX5106
AX5201
AX5203
AX5206
AC supply (max.)
*)
6 A
12 A
20 A
12 A
20 A
20 A
24 V supply (max.)
3 A
Brake resistor
electronic
*) UL-Mains fuses must be used.
Three-phase
Fusing
AX
5101
5103
5106
5112
5118
5125
5140
5201
5203
5206
AC suppl (max.)
*)
6 A
12 A
20 A
20 A
35 A
45 A
80 A
12 A
20 A
20 A
24 V supply (max.)
3 A
Brake resistor
elektronisch
*) UL-Mains fuses must be used.
For alternatives regarding class RK5 UL-fuses, you must observe “UL508 A, chapter
SB4.2.3, exception no. 1”. For further questions regarding UL-fuses, please contact your
responsible certification authority.

Table of Contents

Other manuals for Beckhoff AX5112

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff AX5112 and is the answer not in the manual?

Beckhoff AX5112 Specifications

General IconGeneral
BrandBeckhoff
ModelAX5112
CategoryServo Drives
LanguageEnglish

Related product manuals