BECKHOFF Drive Technology 5 Installation
AX5000 Version 6.2 37
5.2.1.4 Internal protection, UL-compliant
24 V - peripheral voltage
5.2.1.5 External drive system protection
Rule of thumb: Determine the total device rated current, multiply by correction factor and
round it up to the next higher standard level.
Example: 1 x AX5103 + 2 x AX5201 + 2 x AX5203
3 A + 6 A
+ 12 A = 21 x 1,1 = 23,1 A selected 25 A
Special requirements for a drive system
Please note the configuration example in chapter 5.2.4