4 Product description BECKHOFF Drive Technology
24 Version : 4.5 AX5000
4.7.5 X04, X05 - EtherCAT connection
Terminal point
Connection
X04 (IN)
incoming EtherCAT line
X05 (OUT)
outgoing EtherCAT line
4.7.6 X06 – Digital I/Os
CAUTION
Destruction of the AX5000!
This connector is not designed for external power supply. It is supplied via
the 24 V supply (U
p
) of connector X03.
Note
Output current
The specified output currents are maximum values. The actual values
depend on your current configuration.
Terminal point
Connection
Output current
24
Output voltage (U
p
24 V
DC
+)
1 A max.
0
Input 0
1
Input 1
2
Input 2
3
Input 3
4
Input 4
5
Input 5
6
Input 6
7
Input 7 or output (configurable) (U
p
24 V
DC
+)
0.5 A max.
0 V
Output voltage GND (-)