Basics communication
EL600x, EL602x 29Version: 4.6
Startup list
Changes in the local CoE list of the terminal are lost if the terminal is replaced. If a terminal is re-
placed with a new Beckhoff terminal, it will have the default settings. It is therefore advisable to link
all changes in the CoE list of an EtherCAT slave with the Startup list of the slave, which is pro-
cessed whenever the EtherCAT fieldbus is started. In this way a replacement EtherCAT slave can
automatically be parameterized with the specifications of the user.
If EtherCAT slaves are used which are unable to store local CoE values permanently, the Startup
list must be used.
Recommended approach for manual modification of CoE parameters
Make the required change in the System Manager
The values are stored locally in the EtherCAT slave
If the value is to be stored permanently, enter it in the Startup list.
The order of the Startup entries is usually irrelevant.
Fig.17: Startup list in the TwinCAT System Manager
The Startup list may already contain values that were configured by the System Manager based on the ESI
specifications. Additional application-specific entries can be created.
Online/offline list
While working with the TwinCAT System Manager, a distinction has to be made whether the EtherCAT
device is "available", i.e. switched on and linked via EtherCAT and therefore online, or whether a
configuration is created offline without connected slaves.
In both cases a CoE list as shown in Fig. “’CoE online’ tab” is displayed. The connectivity is shown as offline/
online.
If the slave is offline
The offline list from the ESI file is displayed. In this case modifications are not meaningful or
possible.
The configured status is shown under Identity.
No firmware or hardware version is displayed, since these are features of the physical device.
Offline is shown in red.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff EtherCAT EL600x Series and is the answer not in the manual?

Beckhoff EtherCAT EL600x Series Specifications

General IconGeneral
BrandBeckhoff
ModelEtherCAT EL600x Series
CategoryI/O Systems
LanguageEnglish

Related product manuals