19
2
For example, “FC_1” (Fault Code) on the control
panel display indicates Low Battery Voltage and
the remote LED would repeatedly flash once with
a pause until it’s reset or the condition is
corrected. “FC_2” Low Oil Pressure would cause
the remote LED to repeatedly flash twice and
pause. Following is a list of the possible fault
codes.
(FC_1) Low Battery Voltage
(FC_2) Low Oil Pressure
(FC_3) Low Output Voltage
(FC_4) Engine Fails To Start
(FC_5) Low Frequency
(FC_6) Engine Overspeed
(FC_7) High Temperature
(FC_8) Transfer Switch Failure
Resetting the Fault Code Detection System
After correcting the failure indicated by the fault
code, the operator or technician must reset the
fault detection system before the Home Standby
System will operate.
1. Place the SYSTEM switch in the OFF
position for 5 seconds or more.
2. Place the SYSTEM switch in the AUTO
position.
If the fault code is not corrected, the unit will
return to Auto Shutdown and the same fault code
indication(s) will be displayed.
STOPPING THE SYSTEM FOR
MAINTENANCE
1. Ensure the main line disconnect (MLD) is
ON and power is supplied to the UTILITY
CONNECTION lugs of the transfer
switch.
2. Set the generator SYSTEM to OFF.
3. Set the generator main circuit breaker to
OFF.
4. Remove the 15 Amp fuse from the system
control panel.
NOTE: Exercise timer will need to be reset
whenever the control panel fuse is removed.
SEE RESETTING THE EXERCISE TIMER ON
PAGE 13.
WARNING
Turn switch to OFF.
Remove 15 Amp fuse from the system
control panel.
Disconnect spark plug wire from plug.
This will prevent accidental starts.