IX. Repair Parts
All Series 2PV Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require
assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham
products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.
Table 8: Minimum Fan Pressure
Figure 20: Procedure for Measuring Fan Pressure
3. Start boiler and read pressure on manometer when
boiler water temperature reaches operating
temperature. Refer to Table 8 for minimum
readings.
NOTE: If switch drops-out before boiler reaches
temperature or if pressure reading is below
minimum shown in Table 8, check for cracks in hose
or contact your nearest Burnham representative.
4. Stop boiler, remove manometer and reconnect hose
to pressure switch.
ledoMrelioB
rewolBmuminiM
erusserPtelnI
VP302.c.wsehcni04.0-
VP402.c.wsehcni04.0-
VP502.c.wsehcni07.0-
VP602.c.wsehcni07.0-