IV. Gas Piping
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to
boiler. Maximum allowable system pressure is ½
psig. Actual point of delivery pressure may be less;
contact gas supplier for additional information.
Minimum gas valve inlet pressure is listed on rating
label.
2. Maximum gas demand. Table 1 lists boiler input
rate. Also consider existing and expected future gas
utilization equipment (i.e. water heater, cooking
equipment).
Table 1: Rated Input
3. Length of piping and number of ttings. Refer to
Table 2 for maximum capacity of Schedule 40 pipe.
Table 3 lists equivalent pipe length for standard
ttings.
4. Speci c gravity of gas. Gas piping systems for gas
with a speci c gravity of 0.70 or less can be sized
directly from Table 2, unless authority having
jurisdiction speci es a gravity factor be applied. For
speci c gravity greater than 0.70, apply gravity
factor from Table 4. If exact speci c gravity is not
shown choose next higher value.
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA 54/
ANSI Z223.1, or size system using standard
engineering methods acceptable to authority having
jurisdiction.
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local
plumbing codes and requirements of gas supplier. In
absence of such requirements, follow National Fuel
Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/
CGA B149 Installation Codes.
2. Use thread (joint) compounds (pipe dope) resistant
to action of lique ed petroleum gas.
relioB
ledoM
rebmuN
etaRtupnI
]ruohrepteefcibuc[
saG
noitcennoC
eziS
saGlarutaNenaporP/PL
VP30224
VP40268
VP5020312
VP602465
Figure 4B: Boiler Piping for Zone Valve Zoned Heating Systems