19

       
 39 72 99 605 191 NA NA
 46 87 124 715 226 NA NA
 56 103 148 856 270 330 480
 66 124 177 960 303 435 575
 80 149 207 1226 387 490 610
 80+ 174 258 1265 400 510 660

06NA - Compressor for air-cooled units
N - Non-economized compressor
E - Economized compressor
I nom. - Average current draw of the compressor at Eurovent conditions (A)
MHA - Must hold amperes (maximum operating current) at 360 V (A)
LRA - Locked rotor current with across-the-line start (A)
LRA (Y) - Locked rotor current at reduced current (star/delta start-up mode) (A)
LRA (S) 1 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp. - Start-up with reduced current (A) with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit