Table 5B Compressor Electrical Data, 30HXA Units
UNIT SIZE
30HXA
NAMEPLATE
V-Hz
(3 Phase)
COMPRESSOR NUMBERS
A1 B1
RLA LRA RLA LRA
076
208/230-60 * * * *
460-60 64.9 485 64.9 485
575-60 51.9 388 51.9 388
380-60 78.7 536 78.7 536
230-50 * * * *
346-50 * * * *
380/415-50 81.5 605 81.5 605
076-WD
208/230-60 143.8 307 143.8 307
460-60 64.9 153 64.9 153
575-60 51.9 123 51.9 123
380-60 78.7 169 78.7 169
230-50 134.8 305 134.8 305
346-50 89.4 210 89.4 210
380/415-50 81.5 191 81.5 191
086
208/230-60 * * * *
460-60 77.6 580 64.9 485
575-60 62.1 484 51.9 388
380-60 94.0 641 78.7 536
230-50 * * * *
346-50 * * * *
380/415-50 99.2 715 81.5 605
086-WD
208/230-60 171.9 367 143.8 307
460-60 77.6 183 64.9 153
575-60 62.1 147 51.9 123
380-60 94.0 203 78.7 169
230-50 163.9 361 134.8 305
346-50 108.8 248 89.4 210
380/415-50 99.2 226 81.5 191
096
208/230-60 * * * *
460-60 94.8 685 64.9 485
575-60 75.7 548 51.9 388
380-60 114.7 757 78.7 536
230-50 * * * *
346-50 * * * *
380/415-50 119.9 856 81.5 685
096-WD
208/230-60 209.8 433 143.8 307
460-60 94.8 216 64.9 153
575-60 75.5 173 51.9 123
380-60 114.7 239 78.7 169
230-50 198.2 432 134.8 305
346-50 131.4 297 89.4 210
380/415-50 119.9 270 81.5 191
106
208/230-60 * * * *
460-60 115.4 820 64.9 485
575-60 92.2 656 51.9 388
380-60 139.7 906 78.7 536
230-50 * * * *
346-50 * * * *
380/415-50 145.4 960 81.5 605
106-WD
208/230-60 255.5 518 143.8 307
460-60 115.4 259 64.9 153
575-60 92.2 207 51.9 123
380-60 139.7 286 78.7 169
230-50 240.2 485 134.8 305
346-50 159.4 334 89.4 210
380/415-50 145.4 303 81.5 191
116
208/230-60 * * * *
460-60 115.4 820 77.6 580
575-60 92.2 656 62.1 484
380-60 139.7 906 94.0 641
230-50 * * * *
346-50 * * * *
380/415-50 145.4 960 99.2 715
116-WD
208/230-60 255.5 578 171.9 367
460-60 115.4 259 77.6 183
575-60 92.2 207 62.1 147
380-60 139.7 286 94.0 203
230-50 240.2 485 163.9 361
346-50 159.4 334 108.8 248
380/415-50 145.4 303 99.2 226
LEGEND
LRA Locked Rotor Amps
RLA Rated Load Amps
WD Wye-Delta Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.