38 Specifications subject to change without notice. SG-38MARB-01
DIAGNOSIS AND SOLUTION (CONT)
Index
DC Fan Motor (Control chip is in the fan motor)
Power on and when the unit is in standby mode, measure the pin1-pin3 and pin4-pin3 voltage in the fan motor connector. If the voltage value is
not in the range shown in the following table. the PCB is faulty and must be replaced.
DC motor voltage input and output (voltage:220-240V~):
DC motor voltage input and output (voltage: 115V~):
No. Color Signal Voltage
1 Red Vs/Vm 192V~380V
2 --- --- ---
3BlackGND0V
4 White Vcc 13.5~16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 13.5~16.5V
No. Color Signal Voltage
1 Red Vs/Vm 140V~190V
2 --- --- ---
3BlackGND0V
4 White Vcc 13.5~16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG 13.5~16.5V