Table II: Operating limits
Cooling/Heating Refer to outdoor unit installation manual.
Mains power supply
Nominal single-phase voltage 230V ~ 50Hz
Operating voltage limits min. 198V – max. 264V
Dimensions and weight
Table I: Nominal data
• Unit is not suitable for operation in laundry premises.
For sizing of power supply wires and delay type fuses,
refer to the outdoor unit installation instructions.
Mod.
42PHW/42PHQ007
42PHW/42PHQ009 - 012 - 014
42PHW/42PHQ 018 - 024
42PHQ007K
42PHQ009K - 012K - 014K
42PHQ018K - 024K
A mm 790 790 1080
B mm 260 260 295
C mm 186 186 185
kg 8 8.6 14
ELECTRIC POWER INPUT
Cooling only unit
Cooling Heating
WW
42PHW007 32 -
42PHW009 43 -
42PHW012 43 -
42PHW014 43 -
42PHW018 53 -
42PHW024 53 -
Heat pump
42PHQ007 / 42PHQ007K 32 32
42PHQ009 / 42PHQ009K 43 43
42PHQ012 / 42PHQ012K 43 43
42PHQ014 / 42PHQ014K 43 43
42PHQ018 / 42PHQ018K 53 53
42PHQ024 / 42PHQ024K 53 53