The requirements for combustion and ventilation air depend upon
whether furnace is located in a CONFINED or UNCONFINED
space.
UNCONFINED SPACE
An unconfined space must have at least 50 cu ft for each 1000
Btuh of input for all appliances (such as furnaces, clothes dryer,
water heaters, etc.) in the space.
For Example:
58DXT FURNACE
HIGH-FIRE INPUT
BTUH
MINIMUM SQ FT
WITH
7-1/2 FT CEILING
63,000 420
84,000 560
105,000 700
If the unconfined space is constructed unusually tight, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with outdoors. Combustion and
ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless equal or greater amount of air is supplied to the room.
CONFINED SPACE
A confined space is defined as a space whose volume is less than
50 cu ft per 1000 Btuh of total input ratings of all appliances
installed in that space. A confined space MUST have provisions
for supplying air for combustion, ventilation, and dilution of flue
gases using 1 of the following methods.
NOTE: In determining free area of an opening, the blocking
effect of louvers, grilles, and screens must be considered. If free
area of louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.
The size of the openings depends upon whether air comes from
outside of the structure or an unconfined space inside the structure.
1. All air from an unconfined space inside the structure requires
2 openings (for structures not usually tight):
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 3 and Table 2.) The minimum dimension of air
openings shall not be less than 3 in.
b. If the building is constructed unusually tight, a permanent
opening directly communicating with the outdoors shall be
provided. (See item 2 below.)
c. If furnace is installed to obtain return air is taken directly
from hallway or space adjacent to furnace, all air for
combustion must come from outdoors.
2. Air from outside the structure requires 1 of the following
methods:
a. If combustion air is taken from outdoors through 2 vertical
ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of total input for all equipment
within the confined space. (See Fig. 4 and Table 2.)
Fig. 3—Confined Space: Air for Combustion and
Ventilation from an Indoor Unconfined Space
A93387
RETURN
AIR
6 MIN
(FRONT)
SUPPLY AIR
VENT THROUGH ROOF
(CATEGORY I)
1 SQ IN.
PER 1000
BTUH
*
IN DOOR
OR WALL
12 MAX
1 SQ IN.
PER 1000
BTUH
*
IN DOOR
OR WALL
12 MAX
INTERIOR
HEATED
SPACE
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
Minimum of 3 in. when type B-1 vent is used.
UNCONFINED
SPACE
Fig. 4—Confined Space: Air for Combustion and
Ventilation from Outdoors
A93388
DUCTS TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH
*
RETURN
AIR
VENT
THROUGH
ROOF
(CATEGORY I)
D
B
A
C
E
1 SQ IN.
PER 4000
BTUH
DUCT
TO
OUTDOORS
SUPPLY AIR
1 SQ IN.
PER 2000
BTUH
*
DUCTS
TO
OUTSIDE
12 MAX
12 MAX
CONFINED
SPACE
12″
MAX
12″
MAX
1 SQ IN.
PER 4000
BTUH
*
OUTDOORS
1 SQ IN.
PER 4000
BTUH
*
1 SQ IN.
PER 2000
BTUH
*
12 MAX
Use any of the following
combinations of openings:
A & B C & D D & E F & G
NOTE:
*
Minimum dimensions of 3 in.
F
G
5