85
Is LED status light on?
Is there 115V at L1 and L2?
Replace furnace control.
Is door switch closed?
Replace transformer.
Replace door switch.
Is door switch closed?
Check for continuity in wire from circuit
breaker to furnace.
Close circuit breaker and go back to
START.
Is LED status light blinking rapidly without
a pause?
Check for correct line voltage polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
Is LED status light blinking ON/OFF
slowly with a combination of short and
long flashes?
Determine status code. The status code
is a 2 digit number with the first digit
determined by the number of short
flashes and the second digit by the
number of long flashes?
To recall status code briefly remove and reconnect one RED wire from the
draft safeguard switch to display stored status code. You can also recall
the previous status code by momentarily shorting the TEST/TWIN
terminal to Com24V terminal until the LED goes out. LED will flash the
status code of the previous fault or status code #11 (1 short and 1 long
flash) if there was no previous fault. After the control repeats the code 4
times, the control will go through a brief component test sequence. The
inducer will start and run for the entire component test. The HSI, blower
motor FAN speed (AMBER LED boards only) HEAT speed, and COOL
speed will run for 10 15 seconds each. Gas valve and humidifier will not
be turned on.
Was there a previous status code other
than #11?
Go to section below for the status code
that was flashed.
Does the control respond to W, Y1 (if
present), Y/Y2, and G (24V) thermostat
signals?
Run system through a heating or cooling
cycle to check operation. Status codes
are erased after 72 hours.
Is 24V present at W, Y1 (if present), Y/Y2
or G thermostat terminals on the furnace
control?
Check room thermostat or
interconnecting cable.
Disconnect all the thermostat wires from
the furnace control.
Does the problem repeat when using a
jumper wire?
Replace furnace control.
The thermostat is not compatible with the
furnace control. Either install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
NO
YES
YES
YES
YES
YES
YES
YES
START
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
Troubleshooting Guide