Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
*Minimum Load Valve energized. NOTE: These capacity steps may vary due to different capacity
staging sequences.
30RAP UNIT SIZE
CONTROL
STEPS
CAPACITY STEPS CAPACITY %
% Displacement Circuit A Circuit B
010 1 100100
015 1 100100
018
1
2
3
100
50
20*
100
020
1
2
3
100
50
24*
100
025
1
2
3
100
50
29*
100
030
1
2
3
100
50
32*
100
035
1
2
3
4
5
100
77
50
23
9*
54 46
040
1
2
3
4
5
100
73
50
23
11*
47 53
045
1
2
3
4
5
100
74
50
24
12*
47 53
050
1
2
3
4
5
100
75
50
25
14*
50 50
055
1
2
3
4
5
100
73
50
23
13*
46 54
060
1
2
3
4
5
100
75
50
25
16*
50 50
47
46
45
44
43
42
41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED
DEADBAND
STANDARD
DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT Leaving Water Temperature
Fig. 13 — Deadband Multiplier

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 and is the answer not in the manual?

Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060 Specifications

General IconGeneral
BrandCarrier
ModelAQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS 30RAP010-060
CategoryAir Conditioner
LanguageEnglish

Related product manuals