If you are mounting the Cisco ASR 9001 chassis in a 4-post enclosed cabinet, ensure that you have these
clearances around the chassis:
• Rear: Minimum of 3.15 inches (8.00 cm) of clearance
• Sides: Minimum of 6 inches (15.24 cm) of clearance on each side of the chassis.
The following figure shows the side and rear chassis air flow clearance requirements for mounting the Cisco
ASR 9001 Router in a 4-post enclosed rack.
Figure 13: ASR 9001 Clearance Requirements for an Enclosed 4-Post Rack Installation
Temperature and Humidity Guidelines
The operating and nonoperating environmental site requirements are listed in Environmental Specifications.
The router normally operates within the ranges listed in Environmental Specifications; however, if a temperature
measurement is approaching a minimum or maximum parameter, it indicates a potential problem. Maintain
normal operation by anticipating and correcting environmental anomalies before they approach critical values,
by properly planning and preparing your site before you install the router.