Always use shielded cables with metal connector shells for attaching peripherals to the system.
When wires are run for any significant distance in an electromagnetic field, interference can occur between
the field and the signals on the wires. This fact has two implications for the construction of plant wiring:
Bad wiring practice can result in radio interference emanating from the plant wiring.
Strong EMI, especially when it is caused by lightning or radio transmitters, can destroy the signal drivers
and receivers in the chassis, and even create an electrical hazard by conducting power surges through
lines into equipment.
To predict and provide a remedy for strong EMI, consult experts in RFI.
Note
If you use twisted-pair cable in your plant wiring, include a good distribution of grounding conductors to
reduce EMI. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground
conductor for each data signal when applicable.
If the wires exceed the recommended distances, or if wires pass between buildings, give special consideration
to the effect of a lightning strike in your vicinity. The electromagnetic pulse caused by lightning or other
high-energy phenomena can easily couple enough energy into unshielded conductors to destroy electronic
devices. If you have had problems of this sort in the past, you may want to consult experts in electrical surge
suppression and shielding.
The intra-building ports (Copper Based Ethernet Ports) of the equipment or subassembly is suitable for
connection to inside a building or unexposed wiring or cabling only. If the intra-building ports of the equipment
or subassembly is metalically connected to interfaces that connect to the Out Side Plant (OSP) or its wiring,
the metallic-connection MUST NOT be more than 6 meters (approximately 20 feet). These interfaces are
designed for use as intra-building interfaces only (Type 2, 4, or 4a ports as described in GR-1089-CORE) and
require isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection
in order to connect these interfaces metallically to an OSP wiring system.
Caution
Shock and Vibration
The equipment complies with the Earthquake, Office, and Transportation Vibration, and Equipment Handling
Criteria of GR-63-CORE.
Power Source Interruptions
Systems are especially sensitive to variations in voltage supplied by the AC power source. Overvoltage,
undervoltage, and transients (or spikes) can erase data from memory or even cause components to fail. To
protect against these types of problems, power wiring ground conductors should always be properly grounded.
Also, place the system on a dedicated power circuit (rather than sharing a circuit with other heavy electrical
equipment). In general, do not allow the system to share a circuit with any of the following:
Copy machines
Air conditioners
Cisco Catalyst 9300 Series Switches Hardware Installation Guide
39
Preparing for Installation
Shock and Vibration

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco C9300L-24T-4X and is the answer not in the manual?

Cisco C9300L-24T-4X Specifications

General IconGeneral
BrandCisco
ModelC9300L-24T-4X
CategorySwitch
LanguageEnglish

Related product manuals