EasyManuals Logo
Home>Cisco>Switch>MDS 9132T

Cisco MDS 9132T User Manual

Cisco MDS 9132T
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
MDS 9132TRack Type
7.5 lb (3.4 kg)EIA (4-post)
15 lb (6.8 kg)Telco (2 post)
For four-post EIA cabinets (perforated or solid-walled):
The minimum spacing for bend radius for fiber-optic cables should have the front mounting posts
of the cabinet offset from the front door by a minimum of 3 in. (7.6 cm).
The distance between the outside face of the front mounting post and the outside face of the back
mounting post should be 26 to 32 in (66 to 81 cm). to allow for rear bracket installation.
3.0 inches (7.6 cm) between the rear of the chassis and the perforated rear door of the cabinet
(required for airflow in the cabinet, if used).
No clearance is required between the chassis and the sides of the rack or cabinet (no side airflow).
Optional jumper power cords are available for use in a cabinet. See the Jumper Power Cord section.Note
Requirements Specific to Perforated Cabinets
In addition to the requirements listed in the General Requirements for Cabinets and Racks section, perforated
cabinets must meet the following requirements:
The front and rear doors must have at least a 60 percent open area perforation pattern, with at least 15
sq. in. (96.7 sq cm) of open area per rack unit of door height.
We recommend that the roof be perforated with at least 20 percent open area, unless the cabinet only
contains Cisco MDS 9132T switch, in which case the roof does not have to be perforated.
We recommend an open or perforated cabinet floor to enhance cooling but it is not required.
Reference Perforated Cabinet
A perforated cabinet that conforms to the above requirements is available from Rittal Corporation:
Rittal Corporation One Rittal Place Springfield, OH 45504 Phone: (800) 477-4000 Cabinet P/N: Rittal 9969427
Cabinet description: PS-DK/OEM Cabinet Assembly, 1998 x 600 x 1000 (H x W x D) (42U)
Requirements Specific to Solid-Walled Cabinets
In addition to the requirements listed in the General Requirements for Cabinets and Racks section, solid-walled
cabinets must meet the following requirements:
Cisco MDS 9132T Fibre Channel Switch Hardware Installation Guide
18
Cabinet and Rack Installation
Requirements Specific to Perforated Cabinets

Table of Contents

Other manuals for Cisco MDS 9132T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco MDS 9132T and is the answer not in the manual?

Cisco MDS 9132T Specifications

General IconGeneral
BrandCisco
ModelMDS 9132T
CategorySwitch
LanguageEnglish

Related product manuals